i-Chiller 160 - 160 kW Chiller Hire

i-Chiller 160

Request Quote

i-Chiller 160

i-Chiller 160

160 KW process CHILLER HIRE

Temperature range -10°C to 15°C

Our i-Chiller 160 has an integral thermal buffer tank in order to give a controlled band of temperature control to your process system.

This 160 kW chiller offers a wide temperature range of -10°C to 15°C water leaving temperature. The unit is also supplied with an integral process pump, quick-release water and power connections for a fast start-up.

With low noise operation and a compact footprint, the i-Chiller 160 is fully packaged to simplify installation on-site with easy setup and control.

Integrated thermal buffer tank
Coil in tank evaporator
Compact footprint
Plug & play

Specifications

Compare products by selecting an alternative

i-Chiller 160 - 160 kW Chiller Hire

i-Chiller 160

Compare this product to...

Process Fluid Outlet Temperature7 °C
Process Fluid Inlet Temperature12 °C
Ambient Temperature30 °C
Cooling Capacity140 kW
Minimum Fluid Outlet Temperature-10 °C
Maximum Fluid Inlet Temperature35 °C
Minimum Ambient Operating Temperature-5 °C
Maximum Ambient Operating Temperature46 °C
Cooling Capacity -20°c Fluid Outlet +30°c AmbientkW
P3 Pump Performance +7°c Outlet +30°c Ambient23.8 m³/hr
Maximum Fluid Flow Rate - P3 Pump56 m³/hr
Minimum Fluid Flow Rate - P3 Pump12.5 m³/hr
Maximum Power Absorbed70 kW
Electrical Power Connections125 A 5-Pin CEE Plug
Electrical Supply Voltage400 V
Electrical Supply Phases3 PH
Electrical Supply Frequency50
Process Fluid Connections4" Bauer
Sound Pressure62.2 db(A) @10m
Length Inc Frame4635 mm
Width Inc Frame1545 mm
Height Inc Frame2535 mm
Weight Inc Frame2131 kg

Specifications

Alternative Hire Products

Why Choose ICS Cool Energy?

24/7 service

Supporting you all day, every day

Fast delivery

In stock for up to same day delivery

Technical specialists

Process temperature control experts