Data Centre Uses Sustainable Heating Hire To Conduct Tier 3 Chiller Cooling Performance Tests
Temporary Heating Supports Critical Tier 3 Data Centre Chiller Testing
To support critical Tier 3 chiller testing, a data centre required a temporary heating solution capable of creating the thermal conditions needed for accurate system validation. With project timelines dependent on successful testing, ICS Cool Energy delivered a temporary heat pump system that helped enable performance testing under controlled conditions, significantly reducing power consumption and costs compared to traditional electric heating methods.
The Challenge
A data centre needed to carry out critical Tier 3 chiller testing under controlled conditions, requiring a one-month continuous simulation of a full load. With their internal IT heat load insufficient to test the permanent cooling system, to achieve this, they required a reliable temporary heating solution that could help create the required thermal load and enable accurate assessment of chiller performance.
In data centre environments, any delay in validating cooling infrastructure can affect timelines, readiness and the next stages of delivery. The customer therefore needed a temporary solution that could be deployed quickly, operate reliably and support the precise conditions required for testing.
Traditionally, this has been achieved using large electrical heaters. However, with a Coefficient of Performance (COP) of just 1.94, relying on standard electric heating for a month-long test would have resulted in staggering energy consumption and power costs. This highly energy-intensive approach directly conflicted with the facility’s sustainability targets.
The Solution
Recognising the need for a more sustainable and efficient approach, the facility turned to ICS Cool Energy. As the OEM of its rental fleet, ICS Cool Energy combines equipment supply with application expertise and responsive service support. Backed by a nationwide network of qualified technicians and one of the industry’s largest service networks, the company can help customers respond quickly to critical project requirements with local support and dependable delivery.
To replicate the required heat load sustainably, ICS Cool Energy supplied two air-cooled chiller heat pumps with a combined heating capacity exceeding 500 kW. These units were deployed to deliver hot water at 20°C to the facility’s chillers, receiving chilled water back at 14°C, which was enough for the cooling system to seamlessly pass the full-load test.
The Result
Through the rapid deployment of the heat pump solution, the data centre successfully completed its month-long full-load test and achieved its Tier 3 certification.
Importantly, the heat pumps operated with a highly efficient COP of 3.5, outperforming the electric heater alternative. This lowered the energy required for the test and reduced the estimated power costs from £10,100 down to just £5,900, saving both capital and carbon emissions.
Featured Product Categories
Data centre cooling and chiller hire
Requiring low temperatures for continuous operation and peak performance, the requirements for keeping data centres cool are high. Our industrial hire chillers (up to 1.2MW) and portable air conditioning solutions can provide the standard of cooling required to keep data centres running. Our data centre chillers for hire range are designed with the highest levels of efficiency & sustainability in mind and are perfectly suited to being positioned in enclosed spaces such as data centres. The data centre chiller hire range has also been designed and developed to offer the smallest equipment available on the market. This design, coupled with low power consumption, ensures our units are perfect for data centre applications. We have worked in the data centre cooling industry since its inception, providing data centre cooling solutions to AI and pharmaceutical industries regardless of footprint or location. By providing services such as remote monitoring and ongoing maintenance, we are the perfect partner to ensure your data centre operates without interruption or thermal throttling, especially in heat waves.
Heat pump chiller hire
We are specialists in heat pump chiller hire and reverse cycle chillers for both heating and cooling applications. We stock more than 500MW of chillers ready for next day delivery with heat pump chillers ranging from 85kW to 550kW, heating from +10°C to +80°C and cooling from +15°C to -10°C. Our heat pumps are built to a robust critical process specification with integrated pumps, buffer tanks and multiple circuits and compressors preventing the risk of single point failure. Heat pump chillers are protected in purpose built transport frames and skids and can be installed with flanged, camlock or Bauer hoses for rapid onsite installation in all situations. Since 1989 we have been providing heat pump chiller hire services for industrial manufacturing and HVAC applications. Our technical specialists are able to support any job, no matter the size from short term up to nine years. Working with you, our team will provide the best solution for your business. <strong>Why use us as your heat pump chiller hire partner?</strong> Our technically trained engineers are heat pump chiller specialists, so you can rely on them to get your pumps installed right, first time. We provide a detailed site survey, system design, equipment specification, delivery, installation and commissioning. Our chiller hire fleet is on average, less than 1.5 years old, ensuring reliability and modern equipment for your business. The age of the equipment and our engineer’s approach will ensure that it is energy efficient – reducing your energy costs. You could also make further savings by considering a free cooling solution.