i-Chiller 45
Request Quote
i-Chiller 45
i-Chiller 45
45 kW Process Chiller Hire
Our i-Chiller 45, which provides a reduced footprint, lower power usage and is part of a 10 model range capable of offering between 1kW and 50kW of cooling.
This full packaged 45 kW chiller contains a circulation pump and thermal buffer tank capable of receiving variable load conditions and providing stable return temperatures. The units can be supplied with ferrous or non-ferrous circuit, together with a wide range of connecting valves and hoses to help connect on to customers specific systems.
Specifications
Compare products by selecting an alternative
i-Chiller 45 |
Compare this product to... |
||
---|---|---|---|
Process Fluid Outlet Temperature | Process Fluid Outlet Temperature | 7 °C | |
Process Fluid Inlet Temperature | Process Fluid Inlet Temperature | 12 °C | |
Ambient Temperature | Ambient Temperature | 30 °C | |
Cooling Capacity | Cooling Capacity | 39.7 kW | |
Minimum Fluid Outlet Temperature | Minimum Fluid Outlet Temperature | -10 °C | |
Maximum Fluid Inlet Temperature | Maximum Fluid Inlet Temperature | 35 °C | |
Minimum Ambient Operating Temperature | Minimum Ambient Operating Temperature | -5 °C | |
Maximum Ambient Operating Temperature | Maximum Ambient Operating Temperature | 46 °C | |
Cooling Capacity -20°c Fluid Outlet +30°c Ambient | Cooling Capacity -20°c Fluid Outlet +30°c Ambient | kW | |
P3 Pump Performance +7°c Outlet +30°c Ambient | P3 Pump Performance +7°c Outlet +30°c Ambient | 6.8 m³/hr | |
Maximum Fluid Flow Rate - P3 Pump | Maximum Fluid Flow Rate - P3 Pump | 18 m³/hr | |
Minimum Fluid Flow Rate - P3 Pump | Minimum Fluid Flow Rate - P3 Pump | 3.2 m³/hr | |
Maximum Power Absorbed | Maximum Power Absorbed | 21 kW | |
Electrical Power Connections | Electrical Power Connections | 63A 5-Pin CEE Plug | |
Electrical Supply Voltage | Electrical Supply Voltage | 400 V | |
Electrical Supply Phases | Electrical Supply Phases | 3 PH | |
Electrical Supply Frequency | Electrical Supply Frequency | 50 | |
Process Fluid Connections | Process Fluid Connections | 2" Bauer | |
Sound Pressure | Sound Pressure | 55 db(A) @10m | |
Length Inc Frame | Length Inc Frame | 2540 mm | |
Width Inc Frame | Width Inc Frame | 1020 mm | |
Height Inc Frame | Height Inc Frame | 1875 mm | |
Weight Inc Frame | Weight Inc Frame | 800 kg |
Specifications
View and compare
Alternative Hire Products
Why Choose ICS Cool Energy?
24/7 service
Supporting you all day, every day
Fast delivery
In stock for up to same day delivery
Technical specialists
Process temperature control experts